Generation of high voltages at power frequency is essential for testing the efficacy of insulation of High Voltage Apparatus used in Power Systems. The generation and testing is carried out in a laboratory, using High Voltage testing transformers. These testing transformers can either be located indoor or outdoor. Cascade Arrangements of TransformersFigure-1 --- High Voltage Cascade TransformerThe above figure shows a typical cascade arrangement of transformers used to obtain up to 300 kV from three units each rated at 100 kV. The low voltage winding is connected to the primary of the first transformer, and this is connected to the transformer tank which is earthed. One end of the high voltage winding is also earthed through the tank. The high voltage end and a tapping near this end is taken out at the top of the transformer through a bushing, and excites the primary of the second transformer. One end of this winding is connected to the tank of the second transformer to maintain the tank at high voltage. The secondary of this transformer too has one end connected to the tank and at the other end the next stage transformer is fed. This cascade arrangement can be continued further, if a still higher voltage is required but not more than four stages. In addition to the normal windings, namely, the low voltage winding, high voltage winding and a third winding known as meter windings is provided to measure the output voltage. Supply to the units can be obtained from a motor-generator set or through an induction regulator for variation of the output voltage. The rating of the primary or the low voltage windings is usually 230 or 400 V for small units up to 100 kVA. For larger outputs the rating of the low voltage winding may be 3.3 kV, 6.6kV or 11 kV. Figure 1 shows the cascade transformer units in which the first transformer is at the ground potential along with its tank. The second transformer is kept on insulators and maintained at a potential of V2, the output voltage of the first unit above the ground. The high voltage winding of the first unit is connected to the tank of the second unit. The low voltage winding of this unit is supplied from the excitation winding of the first transformer, which is in series with the high voltage winding of the first transformer at its high voltage end. The rating of the excitation windings is almost identical to that of the primary or the low or the low voltage winding. The high voltage connection from the first transformer winding and the excitation winding terminal are taken through a bushing to the second transformer. In a similar manner, the third transformer is kept on insulators above the ground at a potential of 2V2 and is supplied likewise from the second transformer. Typical Short circuit current for the High Voltage test is around 0.1 A for dry tests on solid and liquid insulation. About 1 A may be necessary for wet test on large specimens. Figure-2--Cascade Transformer unit with isolating transformer for excitationT1,T2,T3- Cascade Transformer UnitslS1,lS2,lS3-Isolation Transformer unitsC1,C2,C3-Capacitance Voltage dividers for h.v. measurement after first second and third stagesIn figure Fig. 2, a second scheme for providing the excitation to the second and the third stages is shown. Isolating transformers lS1,lS2,lS3 are 1:1 ratio transformers and are meant for supplying the excitation for the second and the third stages at their tank potentials. Power supply to the isolating transformers is also fed from the same a.c. input. This scheme is expensive and requires more space. The advantage of this scheme is that the natural cooling is sufficient and the transformers are light and compact. Transportation and assembly is easy. Also the construction is identical for isolating transformers and the high voltage cascade units. Three phase connection in delta or star is possible for the three units. Testing transformers of ratings up to 10 MVA are cascade connected to give high voltages up to 2.25 MV are available for both indoor and outdoor applications.
References:
|